About these modbus tools
Modbus is one of the most widely used protocols in industrial automation. Debugging usually means checking frames, computing checksums, or turning captured hex back into readable values. This section gathers four tools for exactly that: RTU and TCP frame parsing (with command building), a CRC16 calculator, and a data type / byte order converter. They are pure calculators — they never touch a device — so you can safely paste field captures. All processing happens in your browser: no network, no upload.
FAQ
Do these tools connect to my device?
No. They only compute and parse; there is no network or serial communication, so they cannot read from or write to a PLC.
Why does my CRC differ from the device?
Make sure the data you feed in excludes the checksum bytes, and that it is appended low byte first (the Modbus RTU convention). Non-standard device implementations can also differ.
The float value looks wrong.
It is almost always a byte order mismatch. Try ABCD, DCBA, BADC and CDAB in turn — one of them is usually correct.
Why does the parser report a CRC mismatch?
The frame may be corrupt, or your copy may be incomplete (for example missing the two trailing checksum bytes). The tool shows the expected value so you can compare.